• +380990100901
  • +380672171677
  • +380674654516
  • mail@general.energy

20.August

Overview of GE GL 312 F1/4031 P and GL 312 F3/4031 P Live Tank Circuit Breakers

https://general.energy/wp-content/uploads/2024/08/gl-312.jpg

The GE GL 312 F1/4031 P and GL 312 F3/4031 P series of live tank circuit breakers are designed for outdoor installation and offer high reliability even under extreme operating conditions. Specifically engineered for low-temperature environments (down to -60°C with a gas mixture and -40°C with pure gas), they incorporate advanced engineering solutions to ensure reliable performance in harsh climates and high-seismic regions.

Key Features and Components

These circuit breakers leverage the latest technologies to significantly enhance efficiency and reliability. A standout feature is the implementation of a double-motion system, reducing energy consumption by 65% during operation. Additionally, the overpressure protection system provides a safe working environment for personnel and substation equipment.

Key components include:

  • Breaker Chamber: Features dual-motion technology and a self-blast system, ensuring stable operation during switching.
  • Pressure Relief System: Offers additional protection for substations and personnel in emergency situations.
  • Temperature-Compensated Status Monitor: Equipped with a two-stage sensor and a three-color indicator for precise monitoring of equipment status.
  • SF6 Check Valves: Installed on each pole to ensure safe handling and management of gas.
  • Aluminum Housing and Galvanized Parts: Provide durability and resistance to corrosion.
  • Spring-Loaded Mechanism with External Position Indicator: Facilitates quick assessment of the switch condition.

Technical characteristics

Rated voltage 145 kV
Lightning surge test voltage (phase-to-ground) 650 kV
Rated frequency 50 Hz
Rated normal current 3150/4000 A
Short circuit trip current rating 40 kA
Rated switch-on current (electrodynamic stability) 104 kA
Duration of short-circuit current flow 3 s
Custom switch-off time 28 ms
Total switch-off time 1.5
Switch-on time < 70 ms
Operating temperature (SF6) -40 °C – +40 °C
Installation height above sea level 1000 m

Easy Installation and Maintenance

One of the advantages of this series is the ease of installation. The GL 312 F1/4031 P and GL 312 F3/4031 P circuit breakers are delivered pre-assembled, significantly reducing commissioning time. Maintenance is also simplified thanks to extended inspection intervals. Additionally, the design allows for the breaker chamber to be serviced without disassembling the entire pole, greatly streamlining maintenance tasks.

Standards Compliance and Certification

GE equipment undergoes rigorous testing in accordance with international IEC and ANSI standards. All development and production stages strictly adhere to ISO 9001, ISO 14001, and OHSAS 18001 standards, verified by regular audits. This guarantees that the final product meets the highest quality and reliability standards.

Benefits for Technicians

Choosing GE’s GL 312 F1/4031 P and GL 312 F3/4031 P circuit breakers is an investment in long-term equipment reliability. With innovative technology, these circuit breakers can perform in even the most demanding environments, making them ideal for businesses looking to minimize downtime and ensure continuous operation of critical systems.

GE’s GL 312 F1/4031 P and GL 312 F3/4031 P series live tank circuit breakers are the optimal choice for businesses needing reliable, low-maintenance, and high-performance outdoor equipment.

Brochure